Knight
Hawk Supply
Your One-Stop Hydraulic Source
Fulflo FV2000 Series Valve
Hydraulic Valves
|
|
|
|
|
|
|
|
|
|
 |
|
|
|
|
|
|
|
|
Fulflo
SVB Series Valve |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
APPLICATION |
|
The Fulflo
“SVB” Series, Underwriter Listed, range in size from 1/4” through 1” and operate
efficiently with liquids of any viscosity at pressures from 7 through 500
P.S.I. The “SVB” valves are of brass construction with threaded connections.
Primarily designed for use with fuel oils on oil burner service, the “SVB”
valves may be used wherever Underwriter Listed valves are required. Each valve
is pre-set to the specified pressure and is equipped with a limiting device
to prevent over-adjustment.
|
|
INSTALLATION |
| Fulflo
valves can be mounted in any position. A tee may be inserted in the pump discharge
line to mount the valve. The correct size of valve should be installed, preferably
matching the pump discharge line. Screw the valve into the nipple in the tee.
When the valve is used for frequent bypassing of oil under pressure, its outlet
should be piped back to the tank. Care must be taken to have the discharge well
below the oil level in the tank to prevent air entrainment and erratic operations.
Only if the valve is used as safety or overload relief and operates infrequently
may its discharge be piped back into the pump suction line. Frequent or continuous
operation under these conditions will cause excessive heating of the oil and
possible damage. |
|
|
|
 |
|
|
|
|
|
ASSEMBLY
NUMBER IDENTIFICATION CHART |
|
 |
|
|
EXAMPLE:
|
|
|
|
S
|
V
|
B
|
-55
|
ZS
|
O
|
|
Underwriter's Listed
|
Series
|
Brass
|
1"
|
Spring
|
Hardened Steel Piston,
Deep Groove
|
|
|
|
|
HOW TO ORDER:
|
|
|
|
Specify:
1. Valve Model Number
2. Spring Letter
3. Piston Number
4. Pressure Setting
NOTE: A definite pressure setting is required due to Underwriter restrictions.
A limiting device is furnished to prevent over-adjustment more than 25% above
set pressure.
|
|
|
|
SETTING VALVES:
|
|
|
|
Valve may be set with a hand
pump for cracking pressure. It will be noted that the maximum set pressure is
limited by the collar “J” soldered to the adjusting screw “C”. If a test stand
is available, valve should be connected to the discharge header with the pump
bypass open, and the bypass gradually closed until the desired pressure registers
on the gauge. Adjust valve adjusting screw until valve slightly bleeds at the
set bypass pressure and lock adjusting screw. If valve is required to bypass
a given amount of fluid at a given pressure, a test stand having a flow meter
in the pump discharge line must be available. With valve adjusted for cracking
pressure as above, continue closing bypass until the required flow registers
on the flow meter and observe pressure. Readjust pressure, if necessary, to
obtain desired pressure at desired flow. |
|
|
|
|
|
 |
|
|
|
|
|